ELECTRICA

Examination of Wind Effect On Adss Cables Aging Test

1.

Department of Electrical & Electronics Engineering, İstanbul University School of Engineering, İstanbul, Turkey

ELECTRICA 2018; 18: 321-324
DOI: 10.5152/iujeee.2018.1818
Read: 1223 Downloads: 635 Published: 03 August 2018

ADSS (All dielectric self supporting) cables are generally installed on high voltage transmission lines and  mostly used under different environmental effects, such as temperature, wind, UV radiation, etc. In this study, wind affect on ADSS cables was investigated by using dry band arcing (IEEE 1222 Electrical surface degradation) test method. A wind source was implemented to the test setup to evaluate the performance of PE (Poly-ethylene) cable jacket on ADSS cable under different wind speeds. Test results indicate that life time of  the ADSS cable decreases while the wind speed is increasing.

Files
EISSN 2619-9831